EchoPump™ Ultrasonic Level Pump Controller
|
LU60-1001
LU60-1061 |
|
This general purpose ultrasonic sensor and controller is well-suited for challenging corrosive, slurry or waste liquids (sodium hypochlorite and wastewater) and for atmospheric bulk storage and waste pump transfer applications. Extremely versatile, its relays can be configured as a single set point alarm, for automatic fill or empty control, for out-of-bounds alarming, or for duplexing pump control. A 16-point linearization function allows for volumetric tank measurement, and classic Flowline intelligence and relay logic provides maximum process safety, no matter the configuration.
|
-Specifications-
| SENSOR |
|
CONTROLLER |
|
| Range: |
0.5' to 33' (15 cm to 10m) |
Display type: |
2-line LCD, 16-digit |
| Accuracy: |
± 0.25% of span in air |
Display units: |
Distance: inch/cm
Volume: gallon/liter |
| Resolution: |
0.125" (3 mm) |
Memory: |
Non-volatile |
| Beam width: |
8° conical |
Supply voltage: |
120/240 VAC @ 50-60 Hz. |
| Dead band: |
0.5' (15 cm) |
Signal output: |
4-20 mA, two-wire |
| Process temp: |
F: -40° to 140°, C: -40° to 60° |
Current flow: |
Isolated, sinking |
| Temp comp: |
Automatic |
Signal invert: |
4-20 or 20-4 mA |
| Electronics temp: |
F: -20° to 140°, C: -4° to 60° |
Calibration: |
Digital, push button |
| Pressure: |
30 psi (2 bar) @ 25°C., derated @ 1.667 psi (.113 bar) per °C.
above 25° C. |
Linearization: |
2-16 points |
| Contact type: |
(5) SPDT relay, latching |
Rec. Cable: |
(5) conductor, shielded |
Contact rating: |
250 VAC @ 10A |
| Cable length: |
150' (48m) max. |
Contact fail-safety: |
Reverts to de-energized state during echo-loss |
| Enclosure rating: |
NEMA 4X (IP65) |
LED indication: |
ower & relay status |
| Installed height: |
4.1" (10.4 cm) |
Electronics temp: |
F: -40° to 140°, C: -40° to 60° |
| Enclosure material: |
PP, UL94VO |
Enclosure: |
NEMA 4X (IP65) |
| Transducer material: |
PVDF Kynar® |
Enclosure material: |
Polycarbonate |
| Mount. threads: |
2" NPT (2" G) |
Conduit entrance: |
1/2" knock outs |
Mount. gasket: |
Viton® (G version only) |
Classification: |
General purpose |
| Conduit entrance: |
Single, 1/2" NPT |
CE Compliance (pending): |
EN 61326 EMC
EN 61010-1 safety |
|
|